Name
Values (Range)
Unit
Step
Default
Description
ResCrvType_UV2
Instantaneous
Frozen timer
Linearly decreased
-
-
Instantaneous
Selection of reset curve type for UV2
tResetDef_UV2
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for definite time
use of UV2
tResetIDMT_UV2
0.00 - 6000.00
s
0.01
0.00
Reset time delay in sec for IDMT curves
for UV2
A_UV2
0.005 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for UV2
B_UV2
0.500 - 99.000
-
0.001
1.000
Parameter B for customer programmable
curve for UV2
C_UV2
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for UV2
D_UV2
0.000 - 10.000
-
0.001
0.000
Parameter D for customer programmable
curve for UV2
P_UV2
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for UV2
Table 330:
CVGAPC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
11.1.6
Monitored data
Table 331:
CVGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
DIROC1
INTEGER
1=Forward
0=Non-
directional
2=Reverse
-
Directional mode of OC1
(nondir, forward,reverse)
DIROC2
INTEGER
1=Forward
0=Non-
directional
2=Reverse
-
Directional mode of OC2
(nondir, forward,reverse)
CURRENT
REAL
-
A
Measured current value
ICOSFI
REAL
-
A
Measured current
multiplied with cos (Phi)
VOLTAGE
REAL
-
kV
Measured voltage value
UIANGLE
REAL
-
deg
Angle between voltage
and current
1MRK502052-UEN B
Section 11
Multipurpose protection
575
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...