The user can select to measure one of the voltage quantities shown in table
Table 333:
Voltage selection for CVGAPC function
Set value for the
parameter
VoltageInput
Comment
1
Phase1
CVGAPC function will measure the phase L1 voltage phasor
2
Phase2
CVGAPC function will measure the phase L2 voltage phasor
3
Phase3
CVGAPC function will measure the phase L3 voltage phasor
4
PosSeq
CVGAPC function will measure internally calculated positive sequence
voltage phasor
5
-NegSeq
CVGAPC function will measure internally calculated negative sequence
voltage phasor. This voltage phasor will be intentionally rotated for 180°
in order to enable easier settings for the directional feature when used.
6
-3ZeroSeq
CVGAPC function will measure internally calculated zero sequence
voltage phasor multiplied by factor 3. This voltage phasor will be
intentionally rotated for 180° in order to enable easier settings for the
directional feature when used.
7
MaxPh
CVGAPC function will measure voltage phasor of the phase with
maximum magnitude
8
MinPh
CVGAPC function will measure voltage phasor of the phase with
minimum magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance voltage, which
is internally calculated as the algebraic magnitude difference between
the voltage phasor of the phase with maximum magnitude and voltage
phasor of the phase with minimum magnitude. Phase angle will be set to
0° all the time
10
Phase1-Phase2
CVGAPC function will measure the voltage phasor internally calculated
as the vector difference between the phase L1 voltage phasor and phase
L2 voltage phasor (U
L1
-U
L2
)
11
Phase2-Phase3
CVGAPC function will measure the voltage phasor internally calculated
as the vector difference between the phase L2 voltage phasor and phase
L3 voltage phasor (U
L2
-U
L3
)
12
Phase3-Phase1
CVGAPC function will measure the voltage phasor internally calculated
as the vector difference between the phase L3 voltage phasor and phase
L1 voltage phasor ( U
L3
-U
L1
)
13
MaxPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the minimum
magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance voltage, which
is internally calculated as the algebraic magnitude difference between
the ph-ph voltage phasor with maximum magnitude and ph-ph voltage
phasor with minimum magnitude. Phase angle will be set to 0° all the
time
It is important to notice that the voltage selection from table
is always applicable
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-ground voltages U
L1
, U
L2
& U
L3
or three
phase-to-phase voltages U
L1L2
, U
L2L3
& U
L3L1
). This information about actual VT
1MRK502052-UEN B
Section 11
Multipurpose protection
577
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...