IEC08000288 V1 EN
Figure 277:
Configuration of the inadvertent energizing function
The setting of the general current and voltage function (typical values) is done as
shown in table
.
Table 336:
The setting of the general current and voltage function
Measured Quantity
Pickup in % of generator
rating
Time delay in seconds
Undervoltage U<
Maximum generator
Phase to Phase
voltage
< 70%
10.0 s
Overvoltage U>
Maximum generator
Phase to Phase
voltage
> 85%
1.0 s
Overcurrent I>
Maximum generator
Phase current
> 50%
0.05 s
In normal operation the overvoltage trip signal is activated and the undervotage trip
signal is deactivated. This means that the overcurrent function is blocked.
When the generator is taken out of service the generator voltage gets low. The
overvoltage trip signal will be deactivated and the undervoltage trip signal will be