13.2.5
Settings
Table 351:
FUFSPVC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OpMode
Off
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
-
-
UZsIZs
Operating mode selection
3U0>
1 - 100
%UB
1
30
Operate level of residual overvoltage
element in % of UBase
3I0<
1 - 100
%IB
1
10
Operate level of residual undercurrent
element in % of IBase
3U2>
1 - 100
%UB
1
30
Operate level of neg seq overvoltage
element in % of UBase
3I2<
1 - 100
%IB
1
10
Operate level of neg seq undercurrent
element in % of IBase
OpDUDI
Off
On
-
-
Off
Operation of change based function
Off/On
DU>
1 - 100
%UB
1
60
Operate level of change in phase voltage
in % of UBase
DI<
1 - 100
%IB
1
15
Operate level of change in phase current
in % of IBase
UPh>
1 - 100
%UB
1
70
Operate level of phase voltage in % of
UBase
IPh>
1 - 100
%IB
1
10
Operate level of phase current in % of
IBase
SealIn
Off
On
-
-
On
Seal in functionality Off/On
USealln<
1 - 100
%UB
1
70
Operate level of seal-in phase voltage in
% of UBase
IDLD<
1 - 100
%IB
1
5
Operate level for open phase current
detection in % of IBase
UDLD<
1 - 100
%UB
1
60
Operate level for open phase voltage
detection in % of UBase
Table 352:
FUFSPVC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
1MRK502052-UEN B
Section 13
Secondary system supervision
609
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...