15.2.5
Settings
Table 494:
TMAGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
PulseTime
0.050 - 60.000
s
0.001
0.150
Output pulse time
OnDelay
0.000 - 60.000
s
0.001
0.000
Output on delay time
OffDelay
0.000 - 60.000
s
0.001
0.000
Output off delay time
ModeOutput1
Steady
Pulsed
-
-
Steady
Mode for output ,1 steady or pulsed
ModeOutput2
Steady
Pulsed
-
-
Steady
Mode for output 2, steady or pulsed
ModeOutput3
Steady
Pulsed
-
-
Steady
Mode for output 3, steady or pulsed
15.2.6
Operation principle
The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3
output signals. The function block incorporates internal logic OR gates in order to
provide grouping of connected input signals to the three output signals from the
function block.
Internal built-in OR logic is made in accordance with the following three rules:
1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value
1 the first output signal (OUTPUT1) will get logical value 1.
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical
value 1 the second output signal (OUTPUT2) will get logical value 1.
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1
the third output signal (OUTPUT3) will get logical value 1.
By use of the settings
ModeOutput1
,
ModeOutput2
,
ModeOutput3
,
PulseTime
,
OnDelay
and
OffDelay
the behavior of each output can be customized. The
OnDelay
is always active and will delay the input to output transition by the set time. The
ModeOutput
for respective output decides whether the output shall be steady with an
drop-off delay as set by
OffDelay
or if it shall give a pulse with duration set by
PulseTime
. Note that for pulsed operation and that the inputs are connected in an OR-
function, a new pulse will only be given on the output if all related inputs are reset and
then one is activated again. For steady operation the
OffDelay
will start when all
related inputs have reset. Detailed logical diagram is shown in figure
1MRK502052-UEN B
Section 15
Logic
801
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...