15.7.2.1
Function block
INDCOMBSPQT
SP_IN*
TIME*
BLOCKED*
SUBST*
INVALID*
TEST*
SP_OUT
IEC15000146.vsd
IEC15000146 V1 EN
Figure 388:
INDCOMBSPQT function block
15.7.2.2
Signals
Table 549:
INDCOMBSPQT Input signals
Name
Type
Default
Description
SP_IN
BOOLEAN
0
Single point indication
TIME
GROUP
SIGNAL
0
Timestamp
BLOCKED
BOOLEAN
0
Blocked for update
SUBST
BOOLEAN
0
Substitued
INVALID
BOOLEAN
0
Invalid value
TEST
BOOLEAN
0
Testmode
Table 550:
INDCOMBSPQT Output signals
Name
Type
Description
SP_OUT
BOOLEAN
Single point indication
15.7.2.3
Technical data
Table 551:
Number of INDCOMBSPQT instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
INDCOMBSPQT
-
10
10
15.7.3
Single point input signal attributes converting function block
INDEXTSPQT
The value part of the single point input signal SI_IN is copied to SI_OUT output. The
time part of single point input is copied to the TIME output. The state bits in the
common part and the indication part of the input signal are copied to the corresponding
state output.
1MRK502052-UEN B
Section 15
Logic
823
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...