15.7.8.3
Settings
Table 571:
RSMEMORYQT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Memory
Off
On
-
-
On
Operating mode of the memory function
15.7.8.4
Technical data
Table 572:
Number of RSMEMORYQT instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
RSMEMORYQT
-
10
30
15.7.9
Set/Reset function block SRMEMORYQT
The Set-reset function (SRMEMORYQT) is a flip-flop with memory that can set or
reset an output from two inputs respectively. Each SRMEMORYQT function block
has two outputs, where one is inverted. The memory setting controls if, after a power
interruption, the flip-flop resets or returns to the state it had before the power
interruption. The
SET
input has priority.
SRMEMORYQT can propagate the quality, the value and the time stamps of the
signals via IEC 61850.
Table 573:
Truth table for SRMEMORYQT function block
SET
RESET
OUT
NOUT
0
0
Last
value
Inverted
last value
0
1
0
1
1
0
1
0
1
1
1
0
If
Memory
parameter is
On
, the output result is stored in semi-retained memory.
15.7.9.1
Function block
SRMEMORYQT
SET
RESET
OUT
NOUT
IEC14000070-1-en.vsd
IEC14000070 V1 EN
Figure 395:
SRMEMORYQT function block
1MRK502052-UEN B
Section 15
Logic
831
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...