15.7.10.1
Function block
TIMERSETQT
INPUT
ON
OFF
IEC14000068-1-en.vsd
IEC14000068 V1 EN
Figure 396:
TIMERSETQT function
15.7.10.2
Signals
Table 578:
TIMERSETQT Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 579:
TIMERSETQT Output signals
Name
Type
Description
ON
BOOLEAN
Output signal, pick-up delayed
OFF
BOOLEAN
Output signal, drop-out delayed
15.7.10.3
Settings
Table 580:
TIMERSETQT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
t
0.000 - 90000.000
s
0.001
0.000
Delay for settable timer n
15.7.10.4
Technical data
Table 581:
Number of TIMERSETQT instances
Logic block
Quantity with cycle time Range or Value
Accuracy
3 ms
8 ms
100 ms
TIMERSETQT
-
10
30
(0.000–90000.000) s
±0.5% ±10 ms
15.7.11
Exclusive OR function block XORQT
The exclusive OR function (XORQT) function is used to generate combinatory
expressions with boolean variables. XORQT function has two inputs and two outputs.
1MRK502052-UEN B
Section 15
Logic
833
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...