5.3.2
Function block
LEDGEN
BLOCK
RESET
NEWIND
ACK
IEC09000321-1-en.vsd
IEC09000321 V1 EN
Figure 4:
LEDGEN function block
GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN
Figure 5:
GRP1_LED1 function block
The GRP1_LED1 function block is an example. The 15 LEDs in each of the three
groups have a similar function block.
5.3.3
Signals
Table 25:
LEDGEN Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Input to block the operation of the LEDs
RESET
BOOLEAN
0
Input to acknowledge/reset the indication LEDs
Table 26:
LEDGEN Output signals
Name
Type
Description
NEWIND
BOOLEAN
New indication signal if any LED indication input is
set
ACK
BOOLEAN
A pulse is provided when the LEDs are
acknowledged
Table 27:
GRP1_LED1 Input signals
Name
Type
Default
Description
HM1L01R
BOOLEAN
0
Red indication of LED1, local HMI alarm group 1
HM1L01Y
BOOLEAN
0
Yellow indication of LED1, local HMI alarm group 1
HM1L01G
BOOLEAN
0
Green indication of LED1, local HMI alarm group 1
1MRK502052-UEN B
Section 5
Local Human-Machine-Interface LHMI
79
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...