tAlarm
and
tWarning
are possible to be defined with a resolution of 10 ms, depending
on the level of the defined values for the parameters.
The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs
freeze if an overflow occurs.
15.15.6.1
Operation accuracy
The accuracy of TEIGAPC depends on essentially three factors
•
function cycle time
•
the pulse length
•
the number of pulses, that is, the number of rising and falling flank pairs
In principle, a shorter function cycle time, longer integrated time length or more pulses
may lead to reduced accuracy.
15.15.6.2
Memory storage
The value of the integrated elapsed time is retained in a non-volatile memory.
15.15.7
Technical data
Table 611:
TEIGAPC Technical data
Function
Cycle time (ms)
Range or value
Accuracy
Elapsed time
integration
3
0 ~ 999999.9 s
±0.2% or ±20 ms
whichever is greater
8
0 ~ 999999.9 s
±0.2% or ±100 ms
whichever is greater
100
0 ~ 999999.9 s
±0.2% or ±250 ms
whichever is greater
Table 612:
Number of TEIGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
TEIGAPC
4
4
4
1MRK502052-UEN B
Section 15
Logic
855
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...