5.4.2
Function block
FNKEYMD1
^LEDCTL1
^FKEYOUT1
IEC09000327 V1 EN
Figure 6:
FNKEYMD1 function block
Only the function block for the first button is shown above. There is a similar block for
every function key button.
5.4.3
Signals
Table 31:
FNKEYMD1 Input signals
Name
Type
Default
Description
LEDCTL1
BOOLEAN
0
LED control input for function key
Table 32:
FNKEYMD1 Output signals
Name
Type
Description
FKEYOUT1
BOOLEAN
Output controlled by function key
5.4.4
Settings
Table 33:
FNKEYMD1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Mode
Off
Toggle
Pulsed
-
-
Off
Output operation mode
PulseTime
0.001 - 60.000
s
0.001
0.200
Pulse time for output controlled by
LCDFn1
LabelOn
0 - 18
-
1
LCD_FN1_ON
Label for LED on state
LabelOff
0 - 18
-
1
LCD_FN1_OFF
Label for LED off state
Table 34:
FNKEYTY1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Type
Off
Menu shortcut
Control
-
-
Off
Function key type
MenuShortcut
Menu shortcut for
function key
1MRK502052-UEN B
Section 5
Local Human-Machine-Interface LHMI
81
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...