Name
Values (Range)
Unit
Step
Default
Description
FrHiHiLim
0.000 - 100.000
Hz
0.001
65.000
High High limit (physical value)
FrHiLim
0.000 - 100.000
Hz
0.001
63.000
High limit (physical value)
FrLowLim
0.000 - 100.000
Hz
0.001
47.000
Low limit (physical value)
FrLowLowLim
0.000 - 100.000
Hz
0.001
45.000
Low Low limit (physical value)
FrLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
UGenZeroDb
1 - 100
%UB
1
5
Zero point clamping in % of UBase
IGenZeroDb
1 - 100
%IB
1
5
Zero point clamping in % of IBase
UAmpComp5
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at 5%
of Ur
UAmpComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at
30% of Ur
UAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at
100% of Ur
IAmpComp5
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at 5%
of Ir
IAmpComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
30% of Ir
IAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
100% of Ir
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of Ir
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of Ir
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of Ir
Table 627:
CMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IL1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation
Off
On
-
-
Off
Operation Mode On / Off
IL1Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IL1RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
IL1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IL2Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IL2RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
Table continues on next page
1MRK502052-UEN B
Section 16
Monitoring
867
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...