16.2.5
Settings
Table 651:
SSIMG Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
PressAlmLimit
1.00 - 100.00
-
0.01
5.00
Alarm setting for pressure
PressLOLimit
1.00 - 100.00
-
0.01
3.00
Pressure lockout setting
TempAlarmLimit
-40.00 - 200.00
-
0.01
30.00
Temperature alarm level setting of the
medium
TempLOLimit
-40.00 - 200.00
-
0.01
30.00
Temperature lockout level of the medium
tPressureAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for pressure alarm
tPressureLO
0.000 - 60.000
s
0.001
0.000
Time delay for pressure lockout indication
tTempAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for temperature alarm
tTempLockOut
0.000 - 60.000
s
0.001
0.000
Time delay for temperture lockout
tResetPressAlm
0.000 - 60.000
s
0.001
0.000
Reset time delay for pressure alarm
tResetPressLO
0.000 - 60.000
s
0.001
0.000
Reset time delay for pressure lockout
tResetTempLO
0.000 - 60.000
s
0.001
0.000
Reset time delay for temperture lockout
tResetTempAlm
0.000 - 60.000
s
0.001
0.000
Reset time delay for temperture alarm
16.2.6
Operation principle
Gas medium supervision SSIMG is used to monitor the gas pressure in the circuit
breaker. Binary inputs of gas density PRES_ALM, PRES_LO, and gas pressure signal
PRESSURE, are taken into account to initiate the alarms PRES_ALM and PRES_LO.
When PRESSURE is less than
PressAlmLimit
or binary signal from CB PRES_ALM
is high then the gas pressure alarm, PRES_ALM will be initiated. Similarly, if
pressure input PRESSURE is less than
PressLOLimit
or binary signal from CB
PRES_LO is high or temperature input TEMP is above lockout level
TempLOLimit
then the gas pressure lockout, PRES_LO will be initiated.
There may be sudden change in pressure of the gas for a very small time, for which the
function need not to initiate any alarm. That is why two time delays
tPressureAlarm
or
tPressureLO
have been included. If the pressure goes below the settings for more than
these time delays, then only the corresponding alarm PRES_ALM or lockout
PRES_LO will be initiated. The SET_P_LO binary input is used for setting the gas
pressure lockout. The PRES_LO output retains the last value until it is reset by using
the binary input RESET_LO. Hysteresis type comparators have been used with the
setting for relative and absolute hysteresis. The binary input BLK_ALM can be used
to block the alarms, and the BLOCK input can block both alarms and the lockout
indication.
Temperature of the medium is available from the input signal of temperature. The
signal is monitored to detect high temperature.
Section 16
1MRK502052-UEN B
Monitoring
892
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...