16.3.2
Functionality
Liquid medium supervision SSIML is used for monitoring the circuit breaker
condition. Binary information based on the oil level in the circuit breaker is used as
input signals to the function. In addition, the function generates alarms based on
received information.
16.3.3
Function block
SSIML
BLOCK
BLK_ALM
LEVEL
TEMP
LVL_ALM
LEVEL_LO
SET_L_LO
SET_T_LO
RESET_LO
LEVEL
LVL_ALM
LVL_LO
TEMP
TEMP_ALM
TEMP_LO
IEC09000128-1-en.vsd
IEC09000128 V1 EN
Figure 424:
SSIML function block
16.3.4
Signals
Table 653:
SSIML Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLK_ALM
BOOLEAN
0
Block all the alarms
LEVEL
REAL
0.0
Level input from CB
TEMP
REAL
0.0
Temperature of the insulation medium from CB
LVL_ALM
BOOLEAN
0
Level alarm signal
LEVEL_LO
BOOLEAN
0
Level lockout signal
SET_L_LO
BOOLEAN
0
Set level lockout
SET_T_LO
BOOLEAN
0
Set temperature lockout
RESET_LO
BOOLEAN
0
Reset level and temperature lockout
Table 654:
SSIML Output signals
Name
Type
Description
LEVEL
REAL
Level service value
LVL_ALM
BOOLEAN
Level below alarm level
LVL_LO
BOOLEAN
Level below lockout level
TEMP
REAL
Temperature of the insulation medium
TEMP_ALM
BOOLEAN
Temperature above alarm level
TEMP_LO
BOOLEAN
Temperature above lockout level
Section 16
1MRK502052-UEN B
Monitoring
894
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...