To protect the SA system from signals with a high change rate that can easily saturate
the EVENT function or the communication subsystems behind it, a quota limiter is
implemented. If an input creates events at a rate that completely consume the granted
quota then further events from the channel will be blocked. This block will be
removed when the input calms down and the accumulated quota reach 66% of the
maximum burst quota. The maximum burst quota per input channel is 45 events per
second.
16.6
Disturbance report DRPRDRE
16.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Analog input signals
A41RADR
-
-
Disturbance report
DRPRDRE
-
-
Disturbance report
A1RADR
-
-
Disturbance report
A2RADR
-
-
Disturbance report
A3RADR
-
-
Disturbance report
A4RADR
-
-
Disturbance report
B1RBDR
-
-
Disturbance report
B2RBDR
-
-
Disturbance report
B3RBDR
-
-
Disturbance report
B4RBDR
-
-
Disturbance report
B5RBDR
-
-
Disturbance report
B6RBDR
-
-
16.6.2
Functionality
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of
all selected analog input and binary signals connected to the function block with a,
maximum of 40 analog and 96 binary signals.
The Disturbance report functionality is a common name for several functions:
1MRK502052-UEN B
Section 16
Monitoring
915
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...