The functions included in the disturbance report are:
•
Event list (EL)
•
Indications (IND)
•
Event recorder (ER)
•
Trip value recorder(TVR)
•
Disturbance recorder (DR)
shows the relations between Disturbance Report, included functions and
function blocks. Event list (EL), Event recorder (ER) and Indications (IND) uses
information from the binary input function blocks (BxRBDR). Trip value recorder
(TVR) uses analog information from the analog input function blocks (AxRADR).
Disturbance recorder DRPRDRE acquires information from both AxRADR and
BxRBDR.
Trip value rec
Event list
Event recorder
Indications
Disturbance
recorder
AxRADR
BxRBDR
Disturbance Report
Binary signals
Analog signals
DRPRDRE
IEC09000337-3-en.vsdx
IEC09000337 V3 EN
Figure 442:
Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list function
is working continuously, independent of disturbance triggering, recording time, and
so on. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary power.
Each report will get an identification number in the interval from 0-999.
1MRK502052-UEN B
Section 16
Monitoring
965
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...