The maximum number of recordings depend on each recordings total
recording time. Long recording time will reduce the number of
recordings to less than 100.
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk
space.
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP or
MMS (over 61850) client. The PC can be connected to the IED front, rear or remotely
via the station bus (Ethernet ports).
Indications (IND)
Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged), see section
""
for more detailed information.
Event recorder (ER)
The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see section
""
for more detailed information.
Event list (EL)
The event list may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see section
""
for more detailed information.
Trip value recorder (TVR)
The recorded trip values include phasors of selected analog signals before the fault and
during the fault, see section
""
for more detailed information.
Disturbance recorder (DR)
Disturbance recorder records analog and binary signal data before, during and after
the fault, see section
""
for more detailed information.
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report
Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
1MRK502052-UEN B
Section 16
Monitoring
967
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...