18.6.9
Status for user defined signals for IEC 60870-5-103
I103USRDEF
18.6.9.1
Functionality
I103USRDEF is a function block with user defined input signals in monitor direction.
Each instance is associated with a Function Type (FUN) and each input signal with an
Information Number (INF). Additionally, all input signals may be defined to use
relative time and how to respond to a GI request.
The user is responsible for assigning a proper FUN value and proper INF values to all
connected inputs. See Settings for details.
18.6.9.2
Identification
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Status for user defined signals for IEC
60870-5-103
I103USRDEF
-
-
18.6.9.3
Function block
I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
RT_START
IEC10000294-3-en.vsdx
IEC10000294 V3 EN
Figure 478:
I103USRDEF function block
18.6.9.4
Signals
Table 761:
I103USRDEF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
INPUT1
BOOLEAN
0
Binary signal Input 1
INPUT2
BOOLEAN
0
Binary signal input 2
INPUT3
BOOLEAN
0
Binary signal input 3
Table continues on next page
1MRK502052-UEN B
Section 18
Station communication
1041
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...