18.6.16
Technical data
Table 787:
IEC 60870-5-103 communication protocol
Function
Value
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
18.7
Horizontal communication via GOOSE for
interlocking GOOSEINTLKRCV
18.7.1
Functionality
GOOSE communication can be used for exchanging information between IEDs via
the IEC 61850-8-1 station communication bus. This is typically used for sending
apparatus position indications for interlocking or reservation signals for 1-of-n
control. GOOSE can also be used to exchange any boolean, integer, double point and
analog measured values between IEDs.