Name
Type
Default
Description
GRP2L2
STRING
-
Second analog input used for phase L2 or L2-L3
quantity
GRP2L3
STRING
-
Third analog input used for phase L3 or L3-L1
quantity
GRP2N
STRING
-
Fourth analog input used for residual or neutral
quantity
Table 862:
SMAI2 Output signals
Name
Type
Description
G2AI3P
GROUP SIGNAL
Group 2 analog input 3-phase group
G2AI1
GROUP SIGNAL
Group 2 analog input 1
G2AI2
GROUP SIGNAL
Group 2 analog input 2
G2AI3
GROUP SIGNAL
Group 2 analog input 3
G2AI4
GROUP SIGNAL
Group 2 analog input 4
G2N
GROUP SIGNAL
Group parameter for residual sample
20.15.4
Settings
Settings
DFTRefExtOut
and
DFTReference
shall be set to default
value
InternalDFTRef
if no VT inputs are available. Internal nominal
frequency DFT reference is then the reference.
Section 20
1MRK502052-UEN B
Basic IED functions
1130
Technical manual