The voltage waveform is then filtered in order to get its RMS value. Note that used
filtering is designed in such a way that it ensures complete removal of the DC current
component which may be present in the primary fault current. The voltage RMS value
is then compared with set Alarm and Trip thresholds. Note that the
TRIP
signal is
intentionally delayed on drop off for 30 ms within the function. The measured RMS
voltage is available as a service value from the function. The function has block and
trip block inputs available as well.
IEC05000301 V1 EN
Figure 46:
Logic diagram for 1Ph High impedance differential protection
HZPDIF
6.2.8
Technical data
Table 53:
HZPDIF technical data
Function
Range or value
Accuracy
Operate voltage
(10-900) V
I=U/R
± 1.0% of I
r
at I ≤ I
r
± 1.0% of I at I > I
r
Reset ratio
>95% at (30-900) V
-
Maximum
continuous power
U>Trip
2
/SeriesResistor ≤200 W
-
Operate time at 0
to 10 x U
d
Min = 5 ms
Max = 15 ms
Reset time at 10
to 0 x U
d
Min = 75 ms
Max = 95 ms
Critical impulse
time
2 ms typically at 0 to 10 x U
d
-
Operate time at 0
to 2 x U
d
Min = 25 ms
Max = 35 ms
Reset time at 2 to
0 x U
d
Min = 50 ms
Max = 70 ms
Critical impulse
time
15 ms typically at 0 to 2 x U
d
-
1MRK502052-UEN B
Section 6
Differential protection
145
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...