Table 70:
ZMHPDIS Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip General
TRL1
BOOLEAN
Trip phase L1
TRL2
BOOLEAN
Trip phase L2
TRL3
BOOLEAN
Trip phase L3
TRPE
BOOLEAN
Trip phase-to-earth
TRPP
BOOLEAN
Trip phase-to-phase
START
BOOLEAN
Start General
STL1
BOOLEAN
Start phase L1
STL2
BOOLEAN
Start phase L2
STL3
BOOLEAN
Start phase L3
STPE
BOOLEAN
Start phase-to-earth
STPP
BOOLEAN
Start phase-to-phase
STTIMER
BOOLEAN
Start timer
7.1.5
Settings
Table 71:
ZMHPDIS Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
DirMode
Off
Offset
Forward
Reverse
-
-
Forward
Direction mode
LoadEncMode
Off
On
-
-
Off
Load encroachment mode Off/On
ReachMode
Overreach
Underreach
-
-
Overreach
Reach mode Over/Underreach
ZnTimerSel
Timers seperated
Timers linked
Internal start
Start from PhSel
External start
-
-
Timers seperated
Zone timer selection
OpModePE
Off
On
-
-
On
Operation mode Off / On of Phase-Earth
loops
ZPE
0.005 - 3000.000
Ohm/p
0.001
30.000
Positive sequence impedance setting for
Phase-Earth loop
ZAngPE
10 - 90
Deg
1
85
Angle for positive sequence line
impedance for Phase-Earth loop
KN
0.00 - 3.00
-
0.01
0.80
Magnitude of earth return compensation
factor KN
KNAng
-180 - 180
Deg
1
-15
Angle for earth return compensation
factor KN
Table continues on next page
1MRK502052-UEN B
Section 7
Impedance protection
179
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...