7.3.5
Settings
Table 87:
ZMFPDIS Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Mode Off / On
RLdFw
0.01 - 5000.00
Ohm/p
0.01
60.00
Resistance determining the load
impedance area - forward
RLdRv
0.01 - 5000.00
Ohm/p
0.01
60.00
Resistance determining the load
impedance area - reverse
XLd
0.01 - 10000.00
Ohm/p
0.01
400.00
Reactance determining the load
impedance area
ArgLd
5 - 70
Deg
1
30
Angle determining the load impedance
area
CVTtype
Any
Passive type
None (Magnetic)
-
-
Passive type
CVT selection determining filtering of the
function
OpModeZ1
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E loops,
zone 1
X1PPZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Positive sequence reactance reach, Ph-
Ph, zone 1
R1PPZ1
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive sequence resistive reach, Ph-Ph,
zone 1
X1PEZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Positive sequence reactance reach, Ph-
E, zone 1
R1PEZ1
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive sequence resistive reach, Ph-E,
zone 1
X0Z1
0.01 - 9000.00
Ohm/p
0.01
100.00
Zero sequence reactance reach, zone 1
R0Z1
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero sequence resistive reach, zone 1
RFPPZ1
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone 1
RFPEZ1
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-E, zone 1
tPPZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase-Phase, zone 1
tPEZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase-Earth, zone 1
IMinOpPPZ1
5 - 6000
%IB
1
10
Minimum operate ph-ph current for
Phase-Phase loops, zone 1
IMinOpPEZ1
5 - 6000
%IB
1
10
Minimum operate phase current for
Phase-Earth loops, zone 1
OpModeZ2
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
-
-
Enable Ph-E PhPh On/Off setting for Ph-Ph and Ph-E loops,
zone 2
X1Z2
0.01 - 3000.00
Ohm/p
0.01
40.00
Positive sequence reactance reach, zone
2
R1Z2
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive sequence resistive reach, zone 2
X0Z2
0.01 - 9000.00
Ohm/p
0.01
120.00
Zero sequence reactance reach, zone 2
R0Z2
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero sequence resistive reach, zone 2
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
208
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...