The protection function can detect earth faults in the entire rotor winding and
associated connections.
Requires injection unit REX060 and a coupling capacitor unit REX061 for correct
operation.
7.8.3
Description of input signals
The inputs to the sensitive rotor earth-fault protection function block are as shown in
table
.
Table 122:
Description of various inputs
Input signal Description
USU
The measured injection voltage. This signal is taken from a pre-processor block, the AI
output. The analog voltage input AI1 is linked to the phase L1 in the pre-processor block
in the Signal Matrix tool.
USI
The measured injection current. This signal is taken from a pre-processor block, the AI
output. In the pre-configured version, the analog voltage input AI2 is linked to the phase
L2 in the pre-processor block in the Signal Matrix tool.
BLOCK
Input to block the function
ZREFSEL
The selection of any of the predefined reference impedances. There is a possibility to
change from one set reference impedance to another. Two different reference
impedances are available.
7.8.4
Description of output signals
The outputs of the sensitive rotor earth-fault protection function block are as shown in
table
.
Table 123:
Description of various outputs
Output signal
Description
TRIP
Common trip command signal
TRIPDC
is the trip command signal at DC-side earth fault
TRIPAC
is the trip command signal at AC-side earth fault
START
is a common signal for both AC and DC side of exciter
STARTDC
is the start signal at DC-side earth fault
STARTAC
is the start signal at AC-side earth fault
ALARM
Signal activated after a set time delay, if the calculated fault resistance gets lower than
the set alarm level
ERROR
Error signal which is boolean with values 0 and 1
ERRSTAT
Status coded signal giving type of error. See table
RAVE
Measured resistance to earth in Ω at an injected frequency (real part of the complex
impedance)
XAVE
Measured reactance to earth in Ω at the injected frequency (imaginary part of the
complex impedance)
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
280
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...