Function
Range or value
Accuracy
Alarm limit of fault resistance
(100 - 1000000)Ω
5% of 1 kΩ at R
f
≤ 1 kΩ
5% of 10 kΩ at 1 kΩ < R
f
≤ 20 kΩ
10% of set value at 20 kΩ < R
f
≤ 200 kΩ
Operate time, start at R
f
~ 0 Ω
and filter length = 1 s
1.00 s typically
-
Operate time, trip at R
f
~ 0 Ω and
filter length = 1 s
3.00 s typically
-
Alarm time delay at R
f
~ 0 Ω and
filter length = 1 s
(0.00 - 600.00) s
±0.2% or ±2.00 s whichever is greater
7.9
100% stator earth fault protection, injection based
STTIPHIZ
7.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
100% stator earth fault protection,
injection based
STTIPHIZ
Rse<
64S
7.9.2
Functionality
The 100% stator earth-fault protection STTIPHIZ is used to detect earth faults in the
stator windings of generators and motors. STTIPHIZ is applicable for generators
connected to the power system through a unit transformer in a block connection. An
independent signal with a certain frequency different from the generator rated
frequency is injected into the stator circuit. The responce of this injected signal is used
to detect stator earth faults.
To implement the above concept, a separate injection box is required. The injection
box generates a square wave voltage signal which for example can be fed into the
secondary winding of the generator neutral point voltage transformer or grounding
transformer. This signal propagates through this transformer into the stator circuit.
The magnitude of the injected voltage signal is measured on the secondary side of the
neutral point voltage transformer or grounding transformer. In addition, the resulting
injected current is measured through a resistive shunt located within the injection box.
These two measured values are fed to the IED. Based on these two measured
quantities, the IED determines the stator winding resistance to ground. The resistance
value is then compared with the preset fault resistance alarm and trip levels.
The protection function can not only detect the earth fault at the generator star point,
but also along the stator windings and at the generator terminals, including the
connected components such as voltage transformers, circuit breakers, excitation
transformer and so on. The measuring principle used is not influenced by the generator
1MRK502052-UEN B
Section 7
Impedance protection
293
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...