7.10.4
Signals
Table 144:
ZGVPDIS Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Connection for current sample signals
U3P
GROUP
SIGNAL
-
Connection for voltage sample signals
BLOCK
BOOLEAN
0
Block of the function
BLKZ
BOOLEAN
0
Block due to fuse failure
BLKUV
BOOLEAN
0
Block of the under voltage seal in
Table 145:
ZGVPDIS Output signals
Name
Type
Description
TRIP
BOOLEAN
General Trip
TRZ1
BOOLEAN
Trip signal Zone 1
TRZ2
BOOLEAN
Trip signal Zone 2
TRZ3
BOOLEAN
Trip signal Zone 3
TRUV
BOOLEAN
Trip from Under voltage seal in
START
BOOLEAN
General start
STZ1
BOOLEAN
Start signal Zone 1
STZ2
BOOLEAN
Start signal Zone 2
STZ3
BOOLEAN
Start signal Zone 3
STUV
BOOLEAN
Start of under voltage seal in
7.10.5
Settings
Table 146:
ZGVPDIS Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
ImpedanceAng
5 - 90
Deg
1
80
Impedance angle in degrees, common for
all zones
IMinOp
5 - 80
%IB
1
10
Minimum operate phase current
OpModeZ1
Off
PP Loops
-
-
PP Loops
Operation mode of Zone 1: Off/Ph-Ph
loops
Z1Fwd
3.0 - 100.0
% Zb
0.1
8.0
Zone 1 forward reach in % of rated
impedance, 100%=full load
Z1Rev
3.0 - 100.0
% Zb
0.1
8.0
Zone 1 reverse reach in % of rated
impedance, 100%=full load
tZ1
0.000 - 60.000
s
0.001
0.000
Time delay to operate for Zone 1
Table continues on next page
Section 7
1MRK502052-UEN B
Impedance protection
320
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...