8.6.4
Signals
Table 186:
SDEPSDE Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current
U3P
GROUP
SIGNAL
-
Group signal for voltage
BLOCK
BOOLEAN
0
Blocks all the outputs of the function
BLKTR
BOOLEAN
0
Blocks the trip outputs of the function
BLKTRDIR
BOOLEAN
0
Blocks the directional operate outputs of the
function
BLKNDN
BOOLEAN
0
Blocks the Non directional current residual outputs
BLKUN
BOOLEAN
0
Blocks the Non directional voltage residual outputs
Table 187:
SDEPSDE Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip of the function
TRDIRIN
BOOLEAN
Trip of the directional residual over current function
TRNDIN
BOOLEAN
Trip of non directional residual over current
TRUN
BOOLEAN
Trip of non directional residual over voltage
START
BOOLEAN
General start of the function
STDIRIN
BOOLEAN
Start of the directional residual over current
function
STNDIN
BOOLEAN
Start of non directional residual over current
STUN
BOOLEAN
Start of non directional residual over voltage
STFW
BOOLEAN
Start of directional function for a fault in forward
direction
STRV
BOOLEAN
Start of directional function for a fault in reverse
direction
STDIR
INTEGER
Direction of fault. A general signal common to all
three mode of residual over current protection
UNREL
BOOLEAN
Residual voltage release of operation of all
directional modes
Section 8
1MRK502052-UEN B
Current protection
390
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...