DIROC2
INTEGER
Directional mode of OC2 (nondir, forward,reverse)
UDIRLOW
BOOLEAN
Low voltage for directional polarization
CURRENT
REAL
Measured current value
ICOSFI
REAL
Measured current multiplied with cos (Phi)
VOLTAGE
REAL
Measured voltage value
UIANGLE
REAL
Angle between voltage and current
11.1.5
Settings
Table 328:
CVGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
CurrentInput
phase1
phase2
phase3
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
-
-
MaxPh
Select current signal which will be
measured inside function
VoltageInput
phase1
phase2
phase3
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
-
-
MaxPh
Select voltage signal which will be
measured inside function
OperHarmRestr
Off
On
-
-
Off
Operation of 2nd harmonic restrain Off /
On
l_2nd/l_fund
10.0 - 50.0
%
1.0
20.0
Ratio of second to fundamental current
harmonic in %
BlkLevel2nd
10 - 5000
%IB
1
5000
Harm analyse disabled above this current
level in % of fundamental current
EnRestrainCurr
Off
On
-
-
Off
Enable current restrain function On / Off
Table continues on next page
Section 11
1MRK502052-UEN B
Multipurpose protection
568
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...