Figure 306:
Data exchange between interlocking modules
When invalid data such as intermediate position, loss of a control IED, or input board
error are used as conditions for the interlocking condition in a bay, a release for
execution of the function will not be given.
On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
For all interlocking modules these general rules apply:
•
The interlocking conditions for opening or closing of disconnectors and earthing
switches are always identical.
•
Earthing switches on the line feeder end, for example, rapid earthing switches, are
normally interlocked only with reference to the conditions in the bay where they
are located, not with reference to switches on the other side of the line. So a line
voltage indication may be included into line interlocking modules. If there is no
line voltage supervision within the bay, then the appropriate inputs must be set to
no voltage
, and the operator must consider this when operating.
•
Earthing switches can only be operated on isolated sections for example, without
load/voltage. Circuit breaker contacts cannot be used to isolate a section, that is,
the status of the circuit breaker is irrelevant as far as the earthing switch operation
is concerned.
•
Disconnectors cannot break power current or connect different voltage systems.
Disconnectors in series with a circuit breaker can only be operated if the circuit
breaker is open, or if the disconnectors operate in parallel with other closed
connections. Other disconnectors can be operated if one side is completely
isolated, or if the disconnectors operate in parallel to other closed connections, or
if they are earthed on both sides.
•
Circuit breaker closing is only interlocked against running disconnectors in its
bay or additionally in a transformer bay against the disconnectors and earthing
Section 14
1MRK502052-UEN B
Control
646
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...