Figure 308:
SCILO function logic diagram
14.2.4
Interlocking for busbar earthing switch BB_ES
14.2.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for busbar earthing switch
BB_ES
-
3
14.2.4.2
Functionality
The interlocking for busbar earthing switch (BB_ES) function is used for one busbar
earthing switch on any busbar parts according to figure
.
QC
en04000504.vsd
IEC04000504 V1 EN
Figure 309:
Switchyard layout BB_ES
1MRK502052-UEN B
Section 14
Control
649
Technical manual