14.2.4.3
Function block
IEC05000347-2-en.vsd
BB_ES
QC_OP
QC_CL
BB_DC_OP
VP_BB_DC
EXDU_BB
QCREL
QCITL
BBESOPTR
BBESCLTR
IEC05000347 V2 EN
Figure 310:
BB_ES function block
14.2.4.4
Logic diagram
EXDU_BB
en04000546.vsd
VP_BB_DC
BB_DC_OP
1
QCREL
QCITL
&
BBESOPTR
BBESCLTR
QC_OP
QC_CL
BB_ES
IEC04000546 V1 EN
14.2.4.5
Signals
Table 371:
BB_ES Input signals
Name
Type
Default
Description
QC_OP
BOOLEAN
0
Busbar earthing switch QC is in open position
QC_CL
BOOLEAN
0
Busbar earthing switch QC is in closed position
BB_DC_OP
BOOLEAN
0
All disconnectors on this busbar part are open
VP_BB_DC
BOOLEAN
0
Status for all disconnectors on this busbar part are
valid
EXDU_BB
BOOLEAN
0
No transm error from bays with disc on this busbar
part
Table 372:
BB_ES Output signals
Name
Type
Description
QCREL
BOOLEAN
Switching of QC is allowed
QCITL
BOOLEAN
Switching of QC is forbidden
BBESOPTR
BOOLEAN
QC on this busbar part is in open position
BBESCLTR
BOOLEAN
QC on this busbar part is in closed position
14.2.5
Interlocking for bus-section breaker A1A2_BS
Section 14
1MRK502052-UEN B
Control
650
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...