Table 497:
ALMCALH Output signals
Name
Type
Description
ALARM
BOOLEAN
OR function betweeen inputs 1 to 16
15.3.5
Settings
Table 498:
ALMCALH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
15.3.6
Operation principle
The logic for group alarm ALMCALH block is provided with 16 input signals and one
ALARM output signal. The function block incorporates internal logic OR gate in
order to provide grouping of connected input signals to the output ALARM signal
from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
ALARM output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
ALARM
Input 1
Input 16
³
1
200 ms
t
IEC13000191-1-en.vsd
IEC13000191 V1 EN
Figure 375:
Group alarm logic
15.3.7
Technical data
Table 499:
Number of ALMCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
ALMCALH
-
-
5
Section 15
1MRK502052-UEN B
Logic
804
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...