When the input goes to 1, the output will be 1 for the time set by the time delay
parameter
t
. Then it returns to 0.
When the output changes value, the time stamp of the output signal is updated.
The supported “quality” state bits are propagated from the input to the output at each
execution cycle. A change of these bits will not lead to an updated time stamp on the
output.
PULSETIMERQT can propagate the quality, value and the time stamps of the signals
via IEC 61850.
15.7.7.1
Function block
PULSETIMERQT
INPUT
OUT
IEC15000145.vsd
IEC15000145 V1 EN
Figure 393:
PULSETIMERQT function block
15.7.7.2
Signals
Table 564:
PULSETIMERQT Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 565:
PULSETIMERQT Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
15.7.7.3
Settings
Table 566:
PULSETIMERQT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Pulse time length
15.7.7.4
Technical data
Table 567:
Number of PULSETIMERQT instances
Logic block
Quantity with cycle time Range or Value
Accuracy
3 ms
8 ms
100 ms
PULSETIMERQT
-
10
30
(0.000–90000.000) s
±0.5% ±10 ms
1MRK502052-UEN B
Section 15
Logic
829
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...