Name
Type
Default
Description
IN5
BOOLEAN
0
Input 5
IN6
BOOLEAN
0
Input 6
IN7
BOOLEAN
0
Input 7
IN8
BOOLEAN
0
Input 8
IN9
BOOLEAN
0
Input 9
IN10
BOOLEAN
0
Input 10
IN11
BOOLEAN
0
Input 11
IN12
BOOLEAN
0
Input 12
IN13
BOOLEAN
0
Input 13
IN14
BOOLEAN
0
Input 14
IN15
BOOLEAN
0
Input 15
IN16
BOOLEAN
0
Input 16
Table 589:
B16I Output signals
Name
Type
Description
OUT
INTEGER
Output value
15.10.4
Monitored data
Table 590:
B16I Monitored data
Name
Type
Values (Range)
Unit
Description
OUT
INTEGER
-
-
Output value
15.10.5
Settings
The function does not have any parameters available in the local HMI or PCM600.
15.10.6
Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of
up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value
according to the table below from 0 to 32768. This follows the general formula: INx
= 2
x-1
where 1≤x≤16. The sum of all the values on the activated INx will be available
on the output OUT as a sum of the integer values of all the inputs INx that are activated.
OUT is an integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it
corresponds to that integer 65535 is available on the output OUT. The B16I function
is designed for receiving up to 16 booleans input locally. If the BLOCK input is
activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
Section 15
1MRK502052-UEN B
Logic
838
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...