compensation at 5, 30 and 100% of rated current. The compensation below 5% and
above 100% is constant and linear in between, see figure
Phase currents (amplitude and angle) are available on the outputs and each amplitude
output has a corresponding supervision level output (ILx_RANG). The supervision
output signal is an integer in the interval 0-4, see section
16.1.7.4
Phase-phase and phase-neutral voltage measurements VMMXU,
VNMMXU
The voltage function must be connected to three-phase voltage input in the
configuration tool to be operable. Voltages are handled in the same way as currents
when it comes to class 0.5 calibrations, see above.
The voltages (phase or phase-phase voltage, amplitude and angle) are available on the
outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section
16.1.7.5
Voltage and current sequence measurements VMSQI, CMSQI
The measurement functions must be connected to three-phase current (CMSQI) or
voltage (VMSQI) input in the configuration tool to be operable. No outputs, other than
X_RANG, are calculated within the measuring blocks and it is not possible to
calibrate the signals. Input signals are obtained from the pre-processing block and
transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (X_RANGE). The output signal is an integer
in the interval 0-4, see section
16.1.8
Technical data
Table 643:
CVMMXN technical data
Function
Range or value
Accuracy
Frequency
(0.95-1.05) × f
r
±
2.0 mHz
Voltage
(0.1-1.5) ×U
r
±
0.5% of U
r
at U
£
U
r
±
0.5% of U at U > U
r
Connected current
(0.2-4.0) × I
r
±
0.5% of I
r
at I
£
I
r
±
0.5% of I at I > I
r
Table continues on next page
Section 16
1MRK502052-UEN B
Monitoring
888
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...