16.9.2
Functionality
The 30 limit counter L4UFCNT provides a settable counter with four independent
limits where the number of positive and/or negative flanks on the input signal are
counted against the setting values for limits. The output for each limit is activated
when the counted value reaches that limit.
Overflow indication is included for each up-counter.
16.9.3
Operation principle
Limit counter (L4UFCNT) counts the number of positive and/or negative flanks on
the binary input signal depending on the function settings. L4UFCNT also checks if
the accumulated value is equal or greater than any of its four settable limits. The four
limit outputs will be activated relatively on reach of each limit and remain activated
until the reset of the function. Moreover, the content of L4UFCNT is stored in flash
memory and will not be lost at an auxiliary power interruption.
16.9.3.1
Design
Figure
illustrates the general logic diagram of the function.
BLOCK
CountType
INPUT
RESET
ERROR
OVERFLOW
LIMIT1 … 4
CounterLimit1...4
MaxValue
OnMaxValue
InitialValue
VALUE
Operation
Counter
Overflow
Detection
Limit
Check
Error
Detection
IEC12000625_1_en.vsd
IEC12000625 V1 EN
Figure 450:
Logic diagram
The counter can be initialized to count from a settable non-zero value after reset of the
function. The function has also a maximum counted value check. The three
possibilities after reaching the maximum counted value are:
1MRK502052-UEN B
Section 16
Monitoring
977
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...