16.9.6
Settings
Table 707:
L4UFCNT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
CountType
Positive edge
Negative edge
Both edges
-
-
Positive edge
Select counting on positive and/or
negative flanks
CounterLimit1
1 - 65535
-
1
100
Value of the first limit
CounterLimit2
1 - 65535
-
1
200
Value of the second limit
CounterLimit3
1 - 65535
-
1
300
Value of the third limit
CounterLimit4
1 - 65535
-
1
400
Value of the fourth limit
MaxValue
1 - 65535
-
1
500
Maximum count value
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
-
-
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
InitialValue
0 - 65535
-
1
0
Initial count value after reset of the
function
16.9.7
Monitored data
Table 708:
L4UFCNT Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
INTEGER
-
-
Counted value
16.9.8
Technical data
Table 709:
L4UFCNTtechnical data
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
Section 16
1MRK502052-UEN B
Monitoring
980
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...