4.5.3
Indication LEDs
The LED indication module comprising 15 LEDs is standard in 670 series. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.
Alarm indication LEDs and hardware associated LEDs are located on the right hand
side of the front panel. Alarm LEDs are located on the right of the LCD screen and
show steady or flashing light.
•
Steady light indicates normal operation.
•
Flashing light indicates alarm.
Alarm LEDs can be configured in PCM600 and depend on the binary logic. Therefore
they can not be configured on the local HMI.
Typical examples of alarm LEDs
•
Bay controller failure
•
CB close blocked
•
Interlocking bypassed
•
SF6 Gas refill
•
Position error
•
CB spring charge alarm
•
Oil temperature alarm
•
Thermal overload trip
The RJ45 port has a yellow LED indicating that communication has been established
between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
4.6
Local HMI setup
The contrast and other settings of the LCD can be adjusted from the local HMI menu
tree. The contrast and other factory settings for the local HMI can be adjusted as follows:
Settings/General settings/HMI/Screen
1MRK506276-UUS B
Section 4
Understand the local human-machine interface
23
Operator's manual