Frequency protection
Table 71. Underfrequency protection SAPTUF
Function
Range or value
Accuracy
Operate value, start function, at symmetrical three
phase voltage
(35.00-75.00) Hz
±2.0 mHz
Operate time, start at f
set
+ 0.02 Hz to f
set
- 0.02 Hz
fn = 50 Hz
Min. = 80 ms
-
Max. = 95 ms
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
- 0.02 Hz to f
set
+ 0.02 Hz
Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time function at f
set
+ 0.02 Hz to
f
set
- 0.02 Hz
(0.000-60.000)s
±0.2% or ±100 ms whichever is greater
Reset time, definite time function at f
set
- 0.02 Hz to f
set
+ 0.02 Hz
(0.000-60.000)s
±0.2% or ±120 ms whichever is greater
Voltage dependent time delay
Settings:
UNom=(50-150)% of U
base
UMin=(50-150)% of U
base
Exponent=0.0-5.0
tMax=(0.010–60.000)s
tMin=(0.010–60.000)s
±1.0% or ±100 ms whichever is greater
(
)
Exponent
U UMin
t
tMax tMin
tMin
UNom UMin
-
=
×
-
+
-
é
ù
ê
ú
ë
û
EQUATION1182 V1 EN
(Equation 3)
U=U
measured
Table 72. Overfrequency protection SAPTOF
Function
Range or value
Accuracy
Operate value, start function at symmetrical three-phase voltage
(35.00-90.00) Hz
±2.0 mHz
Operate time, start at f
set
-0.02 Hz to f
set
+0.02 Hz
fn = 50Hz
Min. = 80 ms
Max. = 95 ms
-
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
+0.02 Hz to f
set
-0.02 Hz
Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time function at f
set
-0.02 Hz to f
set
+0.02 Hz
(0.000-60.000)s
±0.2% ±100 ms
whichever is greater
Reset time, definite time function at f
set
+0.02 Hz to f
set
-0.02 Hz
(0.000-60.000)s
±0.2% ±120 ms,
whichever is greater
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
ABB
87