The current transformer requirements are based on the maximum fault current for
faults in different positions. Maximum fault current will occur for three-phase faults
or single phase-to-earth faults. The current for a single phase-to-earth fault will exceed
the current for a three-phase fault when the zero sequence impedance in the total fault
loop is less than the positive sequence impedance.
When calculating the current transformer requirements, maximum fault current for
the relevant fault position should be used and therefore both fault types have to be
considered.
16.1.4
Secondary wire resistance and additional load
The voltage at the current transformer secondary terminals directly affects the current
transformer saturation. This voltage is developed in a loop containing the secondary
wires and the burden of all relays in the circuit. For earth faults the loop includes the
phase and neutral wire, normally twice the resistance of the single secondary wire. For
three-phase faults the neutral current is zero and it is just necessary to consider the
resistance up to the point where the phase wires are connected to the common neutral
wire. The most common practice is to use four wires secondary cables so it normally
is sufficient to consider just a single secondary wire for the three-phase case.
The conclusion is that the loop resistance, twice the resistance of the single secondary
wire, must be used in the calculation for phase-to-earth faults and the phase resistance,
the resistance of a single secondary wire, may normally be used in the calculation for
three-phase faults.
As the burden can be considerable different for three-phase faults and phase-to-earth
faults it is important to consider both cases. Even in a case where the phase-to-earth
fault current is smaller than the three-phase fault current the phase-to-earth fault can
be dimensioning for the CT depending on the higher burden.
In isolated or high impedance earthed systems the phase-to-earth fault is not the
dimensioning case and therefore the resistance of the single secondary wire always
can be used in the calculation, for this case.
16.1.5
General current transformer requirements
The current transformer ratio is mainly selected based on power system data for
example, maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to be
detected with the selected CT ratio. The minimum operating current is different for
different functions and normally settable so each function should be checked.
The current error of the current transformer can limit the possibility to use a very
sensitive setting of a sensitive residual overcurrent protection. If a very sensitive
setting of this function will be used it is recommended that the current transformer
should have an accuracy class which have an current error at rated primary current that
is less than ±1% (for example, 5P). If current transformers with less accuracy are used
1MRK 505 291-UEN A
Section 16
Requirements
317
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...