L1
IL
1
IL
2
IL
3
L2
L3
Protected Object
CT 600/5
Star Connected
IL1
IL2
IL3
IED
IEC13000002-4-en.vsdx
1
2
3
4
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AI N
5
IN
IEC13000002 V4 EN
Figure 26:
Star connected three-phase CT set with star point towards the protected object
Where:
1)
The drawing shows how to connect three individual phase currents from a star connected
three-phase CT set to the three CT inputs of the IED.
2)
The current inputs are located in the TRM. It shall be noted that for all these current inputs the
following setting values shall be entered for the example shown in
•
CTprim=600A
•
CTsec=5A
•
CTStarPoint=ToObject
Inside the IED only the ratio of the first two parameters is used. The third parameter
(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.
In other words, currents are already measured towards the protected object.
Table continues on next page
1MRK 505 291-UEN A
Section 4
Analog inputs
67
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...