3.1.3
Calculating settings for global base values for setting
function GBSVAL
Each function uses primary base values for reference of settings. The base values are
defined in Global base values for settings function. It is possible to include six Global
base values for settings GBASVAL functions: Global base 1 – Global base 6. In this
application, only Global base 1 is needed for defining the base for all inputs.
For transformer protection, set the parameters for the Global base values for settings
functions according to the power transformer primary rated values:
1.
Set
IBase
to
1000 A
.
2.
Set
UBase
to
145 kV
.
3.
Set
SBase
to
251 MVA
.
3.1.4
Calculating settings for instantaneous phase overcurrent
protection 3-phase output PHPIOC
Instantaneous phase overcurrent protection 3-phase output (PHPIOC) shall give very
fast fault clearance of line short circuits close to the substation.
1.
Set
GlobalBaseSel
to 1
The settings are made in primary values. These values are given in the base
settings in Global base 1.
2.
Set
I>>
to 600 % of
IBase
.
The protection shall not overreach the line and it shall not trip for short circuits
in the reverse direction.
A three-phase short circuit at the remote line end and low source impedance
gives the following fault current to the protection:
145
3
4.0 83
3.2 2.5
17.5
ph
sc
sc
line
U
I
kA
Z
Z
j
j
=
=
=
Ð °
+
+
+
EQUATION2341 V1 EN
Z
sc
is the positive sequence source impedance “behind” the line and Z
line
is the
positive sequence impedance of the line.
A three-phase short circuit at the own busbar (reverse fault) gives the following
fault current to the protection:
145
3
4.0 83
3.2 2.5
17.5
ph
sc
sc
line
U
I
kA
Z
Z
j
j
=
=
=
Ð °
+
+
+
EQUATION2341 V1 EN
Z
sc
is the positive sequence source impedance of the remote substation and Z
line
is the positive sequence impedance of the line.
3.
Set
IP>>
to
600 %
of
IBase
(6000 A primary).
Section 3
1MRK 505 291-UEN A
REQ650 setting examples
46
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...