binary output for a raise pulse command in the Signal Matrix in PCM600 and
monitoring a positive from this output.
4.
After the issue of the raise command, return the applied voltage to
USet
(nominal value).
5.
Raise the voltage 1% above the upper deadband limit U2 and wait for the
issue of a lower command from the voltage control after the expiry of a
constant or inverse time delay set by
t1
. Detection of this command will
involve locating the allocated binary output for a low pulse command in the
Signal Matrix in PCM600 and monitoring a positive from this output.
6.
Return the applied voltage to
USet
.
10.9.4.4
Check the undervoltage block function
SEMOD175185-578 v6
1.
Confirm the setting for
Ublock
, nominally at 80% of rated voltage.
2.
Confirm the voltage control function response to an applied voltage below
Ublock
, by reviewing the setting in the local HMI under
Main menu/
Settings/IED Settings/Control/TransformerVoltageControl(ATCC,90)/
TR1ATCC:x/TR8ATCC:x/UVBk
that may cause an alarm, total or
automatic block of the voltage control function to be displayed on the local
HMI.
3.
Apply a voltage slightly below
Ublock
and confirm the response of the
voltage control function.
10.9.4.5
Check the upper and lower busbar voltage limit
SEMOD175185-588 v6
1.
Confirm the settings for
Umin
and
Umax
in the local HMI under
Main menu/
Settings/IED Settings/Control/TransformerVoltageControl(ATCC,90)/
TR1ATCC:x/TR8ATCC:x/Voltage/Umax or Umin
and
Main menu/
Settings/IED Settings/Control/TR8ATCC (90)/TR8ATCC:n/Voltage/
Umax
2.
Confirm the voltage control function response to an applied voltage below
Umin
and above
Umax
, by reviewing the settings in the local HMI under
Main menu/Settings/IED Settings/Control/
TransformerVoltageControl(ATCC,90)/TR1ATCC:x/TR8ATCC:x/
UVPartBk
and
Main menu/IED Settings/Control/
TransformerVoltageControl/TR1ATCC:x/TR8ATCC:x/OVPartBk
. These
conditions may cause an alarm or total block of the voltage control function
to be displayed on the local HMI.
3.
Decrease the injected voltage slightly below the
Umin
value and check for the
corresponding blocking or alarm condition on the local HMI. For an alarm
condition, the voltage regulation function is not blocked and a raise command
should be issued from the IED.
4.
Increase the applied voltage slightly above the
Umax
value and check for the
corresponding blocking or alarm condition on the local HMI. For an alarm
1MRK 506 377-UEN C
Section 10
Testing functionality by secondary injection
Railway application RER670 2.2 IEC
145
Commissioning manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Page 2: ......
Page 26: ...20...
Page 54: ...48...
Page 58: ...52...
Page 62: ...56...
Page 80: ...74...
Page 188: ...182...
Page 194: ...188...
Page 204: ...198...
Page 214: ...208...
Page 215: ...209...