Headline
Explanation
Time diff: IED vs Sampled value
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
Frequency diff: IED vs Sampled value
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the
same as given in PCM600, e.g. AP1: MU1_9201
svID: <ABB_MU0101>
Wrong cycle time for PMU report
Wrong cycle time on SMAI or 3PHSUM block
connected to Phasor Report block. The SMAI or
3PHSUM block should have the same cycle time
as that of Phasor Report.
PMU not connected to 3ph output
The PMU phasor report input(s) must be
connected to the 3ph output of SMAI or 3PHSU.
Invalid value set for PMU Parameters
There are two explanations possible:
Check if the following parameters are set
correctly on PMUREPORT:
ReportRate or
SvcClass or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set
correctly on PMUREPORT:
ReportRate or
SvcClass or RptTimetag or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Invalid phase angle reference
The selected
PhaseAngleRef corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
GOOSE is configured on a disabled port
At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point
operation to off or by unchecking the GOOSE
protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
LDCM not running the application image
<slot number> is running the factory image
instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
LDCM version is not accepted
<device name> firmware version <version
string> is not accepted. The minimum accepted
version is <version string>.
Please update the LDCM firmware or replace the
board.
OEM not running the application image
OEM in slot <slot number> is running the factory
image instead of the application image. The
factory image is older and does not contain the
latest updates and fixes.
Please reboot the IED. If the problem persists,
update the OEM firmware or replace the board.
Table continues on next page
Section 12
1MRK 506 377-UEN C
Troubleshooting
194
Railway application RER670 2.2 IEC
Commissioning manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Page 2: ......
Page 26: ...20...
Page 54: ...48...
Page 58: ...52...
Page 62: ...56...
Page 80: ...74...
Page 188: ...182...
Page 194: ...188...
Page 204: ...198...
Page 214: ...208...
Page 215: ...209...