There are no settings needed for the IEC/UCA 61850-9-2LE communication in the
local HMI branch
Station communication
. Make sure that the optical fibers are
connected correctly. Communication is enabled whenever the merging unit starts
sending data.
8.3
Verifying the communication
SEMOD172108-24 v11
To verify that the communication is working a test/analyzing tool, for example
ITT600, can be used.
Verifying redundant IEC 61850-8-1 communication
Ensure that the IED receives IEC 61850-8-1 data on the selected Ethernet ports.
Browse in the local HMI to
Main menu/Diagnostics/Communication/Ethernet
status/Access point/APStatusRedundant/RCHLCCH:1
and check that
ChARedStatus and ChBRedStatus are shown as
Ok
. Remove the optical
connection to one of the Ethernet ports. Verify that either signal status (depending
on which connection that was removed) is shown as
Error
and the that other signal
is shown as
Ok
. Be sure to re-connect the removed connection after completed
verification.
Section 8
1MRK 506 377-UEN C
Establishing connection and verifying the IEC 61850 communication
58
Railway application RER670 2.2 IEC
Commissioning manual