10.4.2
Distance protection zone, quadrilateral characteristic
ZRWPDIS
GUID-9C7EEB4D-95AE-479B-A835-108B817F803F v2
Prepare the IED for verification of settings outlined in Section
Values of the logical signals for ZRWPDIS are available on the local HMI under
Main menu/Test/Function status/Impedance protection//
DistanceProt2Ph(21,Z<)/ZRWPDIS(21;Z<):1
.
The Signal Monitoring tool in PCM600 shows same signals that are available on
the Local HMI.
10.4.2.1
Verifying the signals and settings
Testing the underimpedance starting element
GUID-1EC21698-A754-450C-A622-65032F277DD1 v1
Measure operating characteristics during constant current conditions. Keep the
measured current as close as possible to its rated value or lower. But make sure it is
higher than the set minimum operating current.
Ensure that the maximum continuous current to the IED does not exceed four times
its rated value, if the measurement of the operating characteristics runs under
constant voltage conditions.
The test procedure has to take into consideration that the shaped load encroachment
characteristic is active. It is therefore necessary to check the setting. To verify the
settings with the shaped load encroachment characteristic, the test should be carried
out according to figures mentioned below. In cases where the load encroachment
characteristic is not activated, tests according to the adjusted figures should be
carried out.
To verify the settings, the operating points according to the following fault types
should be tested:
•
One phase-to-earth fault
•
One phase-to-phase fault
Set
Operation
to On always to check for performance of distance protection during
testing.
Solidly earthed system
GUID-BA73C09D-C911-49C7-91EE-EFC2786819FD v1
1.
Select type of earthing system by setting parameter
SystemEarthing
and set to
Solidly.
2.
Select
CharStartZ<
to Circular and set
OpLoadEnch
to On.
3.
Set
Z1CircleStart
,
REOverRLStart
,
XEOverXLStart
,
LineAng
and
ArgLd
to
default values. Also, set
RLd
such that its value is lower than
Z1CircleStart
.
Phase-to-earth fault - circular characteristic
GUID-71442735-195E-4B9B-A5FE-3E6BDCA8C023 v1
Section 10
1MRK 506 377-UEN C
Testing functionality by secondary injection
82
Railway application RER670 2.2 IEC
Commissioning manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Page 2: ......
Page 26: ...20...
Page 54: ...48...
Page 58: ...52...
Page 62: ...56...
Page 80: ...74...
Page 188: ...182...
Page 194: ...188...
Page 204: ...198...
Page 214: ...208...
Page 215: ...209...