circuit breaker open an auto reclosing start pulse is generated and latched in the
function, subject to the usual checks. The auto reclosing sequence continues then as
usual. Signals from manual tripping and other functions, which shall prevent auto
reclosing, need to be connected to the
INHIBIT
input.
12.2.2.4
Blocking of the auto recloser
M12391-103 v4
Auto reclose attempts are expected to take place only for faults on the own line.
The auto recloser must be blocked by activating the
INHIBIT
input for the
following conditions:
•
Tripping from delayed distance protection zones
•
Tripping from back-up protection functions
•
Tripping from breaker failure function
•
Intertrip received from remote end circuit breaker failure function
•
Busbar protection tripping
Depending of the starting principle (general trip or only instantaneous trip) adopted
above the delayed and back-up zones might not be required. Breaker failure trip
local and remote must however always be connected.
12.2.2.5
Control of the auto reclosing dead time for shot 1
M12391-113 v5
For the first shot, there is a separate setting for the dead time,
t1
. If no particular
input signal is applied, the auto reclosing dead time
t1
will be used. There is also a
separate time setting facility for high-speed auto reclosing without synchrocheck,
t1_HS
, available for use when required. It is activated by the
STARTHS
input.
12.2.2.6
Long trip signal
M12391-117 v4
When start pulse duration signal is longer than set maximum start pulse duration,
the auto reclosing sequence interrupts in the same way as for a signal to the
INHIBIT
input.
12.2.2.7
Maximum number of reclosing shots
M12391-120 v7
The maximum number of auto reclosing shots in an auto reclosing cycle is selected
by the setting
NoOfShots
. A maximum of five shots can be done.
12.2.2.8
Auto reclosing reclaim timer
M12391-202 v4
The
tReclaim
timer defines the time it takes from issue of the breaker closing
command, until the auto recloser resets. Should a new trip occur during this time, it
is treated as a continuation of the first fault. The reclaim timer is started when the
circuit breaker closing command is given.
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
227
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...