INHIBOUT
If the
INHIBIT
input is activated it is reported on the
INHIBOUT
output.
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit
breaker close command.
READY
Indicates that the auto recloser is ready for a new and complete auto reclosing
sequence. It can be connected to the zone extension if a line protection should have
extended zone reach before auto reclosing.
SETON
Indicates that auto recloser is switched on and operative.
SUCCL
If the circuit breaker closing command is given and the circuit breaker is closed
within the set time interval
tUnsucCl
, the
SUCCL
output is activated after the set
time interval
tSuccessful
.
SYNCFAIL
The
SYNCFAIL
output indicates that the auto recloser is inhibited because the
synchrocheck or energizing check condition has not been fulfilled within the set
time interval, tSync. Also
ABORTED
output will be activated.
UNSUCCL
Indicates unsuccessful reclosing.
Connection and setting examples
Figure
shows an example of how to connect the auto recloser.
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
233
Application manual