If there is no second busbar B at the other side of the transformer and therefore no
QB4 disconnector, then the state for QB4 is set to open by setting the appropriate
module inputs as follows:
•
QB4_OP = 1
•
QB4_CL = 0
12.4.5
Interlocking for bus-section breaker A1A2_BS
IP14154-1 v2
12.4.5.1
Application
M15110-3 v7
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure
can be used for different busbars, which includes a bus-section circuit breaker.
QA1
WA1 (A1)
QB2
QC4
QB1
QC3
WA2 (A2)
en04000516.vsd
QC2
QC1
A1A2_BS
IEC04000516 V1 EN-US
Figure 96:
Switchyard layout A1A2_BS
M15111-4 v3
The signals from other bays connected to the module A1A2_BS are described
below.
12.4.5.2
Signals from all feeders
M15111-6 v4
If the busbar is divided by bus-section circuit breakers into bus-sections and both
circuit breakers are closed, the opening of the circuit breaker must be blocked if a
bus-coupler connection exists between busbars on one bus-section side and if on
the other bus-section side a busbar transfer is in progress:
Section 12
1MRK 506 375-UEN A
Control
268
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...