D
U is the deadband setting in percent.
•
n
denotes the desired number of difference in tap position between the
transformers, that shall give a voltage deviation U
di
which corresponds to the
dead-band setting.
•
p
is the tap step (in percent of transformer nominal voltage).
•
a
is a safety margin that shall cover component tolerances and other non-linear
measurements at different tap positions (for example, transformer reactances
changes from rated value at the ends of the regulation range). In most cases a
value of a = 1.25 serves well.
This calculation gives a setting of
Comp
that will always initiate an action (start
timer) when the transformers have n tap positions difference.
OperSimTap
: Enabling/disabling the functionality to allow only one transformer at
a time to execute a Lower/Raise command. This setting is applicable only to the
circulating current method, and when enabled, consecutive tap changes of the next
transformer (if required) will be separated with the time delay
t2
.
OperUsetPar
: Enables/disables the use of a common setting for the target voltage
USet
. This setting is applicable only to the circulating current method, and when
enabled, a mean value of the
USet
values for the transformers in the same parallel
group will be calculated and used.
OperHoming
: Enables/disables the homing function. Applicable for parallel control
with the circulating current method, as well for parallel control with the master-
follower method.
VTmismatch
: Setting of the level for activation of the output VTALARM in case
the voltage measurement in one transformer bay deviates to the mean value of all
voltage measurements in the parallel group.
tVTmismatch
: Time delay for activation of the output VTALARM.
T1RXOP.......T8RXOP
: This setting is set
On
for every transformer that can
participate in a parallel group with the transformer in case. For this transformer
(own transformer), the setting must always be
Off
.
TapPosOffs
: This setting gives the tap position offset in relation to the master so
that the follower can follow the master’s tap position including this offset.
Applicable when regulating in the follow tap command mode.
MFPosDiffLim
: When the difference (including a possible offset according to
TapPosOffs
) between a follower and the master reaches the value in this setting,
then the output OUTOFPOS in the Automatic voltage control for tap changer,
parallel control TR8ATCC function block of the follower will be activated after the
time delay
tMFPosDiff
.
Section 12
1MRK 506 375-UEN A
Control
330
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...